LINE: ask a price

Microfiber

Microfiber MicroCover glass-wool pipe section

Pre-formed glass-wool pipe section for steam, hot-water and chilled-water pipes, 1 m per piece, for iron and copper pipe.

Thermal conductivity (λ)
0.030 / 0.032 / 0.033 / 0.038 / 0.043 / 0.046 / 0.051 / 0.056 / 0.062 / 0.069 / 0.075 W/m·K at 10 / 24 / 38 / 66 / 93 / 121 / 149 / 177 / 204 / 232 / 260 °C mean (test standard not stated)
Maximum service temperature
232 °C for the standard (Plain) 64 kg/m³ type · the Hi-Temperature type (above 80 kg/m³, special order) is rated −18 to 450 °C ASTM C411

Ask us on LINE about the sizes we supply and the price.

Ask about this product

Product details

Pipe insulationGlass wool (fibreglass)Microfiber

Pre-formed glass-wool pipe section, unfaced · 1 m long

Thermal conductivity (λ)
0.030 / 0.032 / 0.033 / 0.038 / 0.043 / 0.046 / 0.051 / 0.056 / 0.062 / 0.069 / 0.075 W/m·K at 10 / 24 / 38 / 66 / 93 / 121 / 149 / 177 / 204 / 232 / 260 °C mean (test standard not stated)
Maximum service temperature
232 °C for the standard (Plain) 64 kg/m³ type · the Hi-Temperature type (above 80 kg/m³, special order) is rated −18 to 450 °C ASTM C411

What is it?

MicroCover from Microfiber is a rigid glass-wool pipe section, 1 m standard length and 64 kg/m³ standard density, slit along one side so it opens over the pipe. It reduces heat or cold loss on steam, hot-water and chilled-water pipes inside and outside buildings, factories, hotels and hospitals. This version is unfaced.

What is it made of?

Glass wool (fibreglass) · Pipe section

Limitations to know

The standard type (Plain, 64 kg/m³) is stated by the maker for hot-water pipes at 232 °C; the −18 to 450 °C range belongs to the Hi-Temperature type, a special-order product.

Where does the data come from?

MicroCover datasheet (MI 04/12)

Technical data from the manufacturer's documents Microfiber · Checked 12 Oct 2026

Technical specifications

All values come from the manufacturer's documents, with conditions and test standards. Values the documents do not state are not shown.

PropertyValueConditions / standardSource
Thermal conductivity (λ)0.030 / 0.032 / 0.033 / 0.038 / 0.043 / 0.046 / 0.051 / 0.056 / 0.062 / 0.069 / 0.075 W/m·Kat 10 / 24 / 38 / 66 / 93 / 121 / 149 / 177 / 204 / 232 / 260 °C mean (test standard not stated)MicroCover datasheet (MI 04/12), p. 2
Maximum service temperature232 °C for the standard (Plain) 64 kg/m³ type · the Hi-Temperature type (above 80 kg/m³, special order) is rated −18 to 450 °CASTM C411MicroCover datasheet (MI 04/12), p. 1
Density64 (standard) · 56–112 can be produced kg/m³—MicroCover datasheet (MI 04/12), p. 2
Dimensions1 m long · iron pipe 1/2–20 in (OD 21.7–508.0 mm) · copper pipe 5/8–6 1/8 in (OD 15.88–158.00 mm)—MicroCover datasheet (MI 04/12), p. 2
Reaction to fireFlame spread 25 · Smoke developed 50ASTM E84MicroCover datasheet (MI 04/12), p. 1
Water vapour sorption< 1.0% at 49 °C, 95% RHASTM C1104MicroCover datasheet (MI 04/12), p. 1
Standards / certificationTIS 486, 488 · ASTM—MicroCover datasheet (MI 04/12), p. 1

Applications

Highlights

  • Pre-formed, 1 m long
  • Sizes for iron and copper pipe
  • k published at 10–260 °C mean

Manufacturer documents