Your selection
SCG PCI unfaced · 25 mm
- Thickness (mm)
- 25
- Density (kg/m³)
- 64
- Length (mm)
- 1000
- Pipe size
- NPS 1/2" – 18"
- Iron pipe size (inch)
Sound coming in or going out (sound insulation)
Echoey rooms (sound absorption)

Pre-formed glass-wool section for steel pipes — hot, cold and exposed piping operating at 10–540 °C.
Iron pipes are named by a nominal size in inches, not the measured size: a 1/2 in pipe measures about 21 mm across the outside.
3. Pipe diameter
Choose the pipe size first; it is shown here.
No size chosen yet
Answer every step above to ask about that exact item, or ask without choosing.
Ask about this productYour selection
Your selection
Your selection
Your selection
Your selection
Your selection
See all models and sizesManufacturer documentsTechnical specifications
Pre-formed glass-wool section for iron pipe · PCI unfaced · PCIF aluminium-foil faced
SCG PCI is a pre-formed glass-wool section for steel pipes operating at 10–540 °C, in commercial buildings, factories, offices, department stores, hospitals, hotels and homes. Density 64 kg/m³; 25, 38 and 50 mm thick; 1 m long; for 1/2" to 18" pipe.
Glass wool (fibreglass) · Pipe section
Thickness 25–50 mm · 64 kg/m³ — Choose a size
SCG thermal insulation catalogue for air-conditioning and industrial work (pages 13–17: pipe insulation)
Technical data from the manufacturer's documents SCG · Checked 26 Sept 2026
All values come from the manufacturer's documents, with conditions and test standards. Values the documents do not state are not shown.
| Property | Value | Conditions / standard | Source |
|---|---|---|---|
| Thermal conductivity (λ) | 0.032 / 0.039 / 0.046 / 0.063 W/m·K | at 24 / 66 / 121 / 204 °C mean (test standard not stated) | SCG thermal insulation catalogue for air-conditioning and industrial work (pages 13–17: pipe insulation), p. 16 |
| Service temperature range | 10 – 540 °C | — | SCG thermal insulation catalogue for air-conditioning and industrial work (pages 13–17: pipe insulation), p. 13 |
| Reaction to fire | FS < 25 · SD < 50 | flame spread / smoke developed · ASTM E84 | SCG thermal insulation catalogue for air-conditioning and industrial work (pages 13–17: pipe insulation), p. 16 |
| Moisture sorption | 0.2% by volume | ASTM C1104 | SCG thermal insulation catalogue for air-conditioning and industrial work (pages 13–17: pipe insulation), p. 16 |
| Model | Thickness (mm) | Density (kg/m³) | Length (mm) | Pipe size |
|---|---|---|---|---|
| PCI | 25 | 64 | 1000 | NPS 1/2" – 18" |
| PCI | 38 | 64 | 1000 | NPS 1/2" – 18" |
| PCI | 50 | 64 | 1000 | NPS 1/2" – 18" |
| PCIF | 25 | 64 | 1000 | NPS 1/2" – 18" |
| PCIF | 38 | 64 | 1000 | NPS 1/2" – 18" |
| PCIF | 50 | 64 | 1000 | NPS 1/2" – 18" |
Pack quantities and prices — ask us on LINE