Pipe insulation · Glass wool
SCG PCI / PCIF
- Pipe size
- ½–18 in
- Thickness
- 25–50 mm
- Service temp.
- 10 – 540 °C
Sound coming in or going out (sound insulation)
Echoey rooms (sound absorption)

Foil-faced pre-formed glass-wool pipe section for steam, hot-water and chilled-water pipes, 1 m per piece; the foil facing protects against moisture.
Ask us on LINE about the sizes we supply and the price.
Ask about this productPre-formed glass-wool pipe section, factory aluminium-foil facing · 1 m long
MicroCover from Microfiber is a rigid glass-wool pipe section, 1 m standard length and 64 kg/m³ standard density. This version is factory-faced with aluminium foil for moisture protection; it is slit along one side with a facing flap to cover the joint, which is then sealed with aluminium tape. The maker gives a facing temperature limitation of −20 to 116 °C (ASTM C1136).
Glass wool (fibreglass) · Facing: Factory-applied aluminium foil · Pipe section
The standard type (Plain, 64 kg/m³) is stated by the maker for hot-water pipes at 232 °C; the −18 to 450 °C range belongs to the Hi-Temperature type, a special-order product.
MicroCover datasheet (MI 04/12)
Technical data from the manufacturer's documents Microfiber · Checked 12 Oct 2026
All values come from the manufacturer's documents, with conditions and test standards. Values the documents do not state are not shown.
| Property | Value | Conditions / standard | Source |
|---|---|---|---|
| Thermal conductivity (λ) | 0.030 / 0.032 / 0.033 / 0.038 / 0.043 / 0.046 / 0.051 / 0.056 / 0.062 / 0.069 / 0.075 W/m·K | at 10 / 24 / 38 / 66 / 93 / 121 / 149 / 177 / 204 / 232 / 260 °C mean (test standard not stated) | MicroCover datasheet (MI 04/12), p. 2 |
| Maximum service temperature | 232 °C for the standard (Plain) 64 kg/m³ type · the Hi-Temperature type (above 80 kg/m³, special order) is rated −18 to 450 °C | ASTM C411 | MicroCover datasheet (MI 04/12), p. 1 |
| Density | 64 (standard) · 56–112 can be produced kg/m³ | — | MicroCover datasheet (MI 04/12), p. 2 |
| Dimensions | 1 m long · iron pipe 1/2–20 in (OD 21.7–508.0 mm) · copper pipe 5/8–6 1/8 in (OD 15.88–158.00 mm) | — | MicroCover datasheet (MI 04/12), p. 2 |
| Reaction to fire | Flame spread 25 · Smoke developed 50 | ASTM E84 | MicroCover datasheet (MI 04/12), p. 1 |
| Water vapour sorption | < 1.0% at 49 °C, 95% RH | ASTM C1104 | MicroCover datasheet (MI 04/12), p. 1 |
| Facing water vapour permeance | 0.02 perm | ASTM E96 | MicroCover datasheet (MI 04/12), p. 1 |
| Facing temperature limitation | −20 to 116 °C | ASTM C1136 | MicroCover datasheet (MI 04/12), p. 1 |
| Standards / certification | TIS 486, 488 · ASTM | — | MicroCover datasheet (MI 04/12), p. 1 |
Send the area details or site photos — we'll suggest the model and quantity
Ask via LINECheck the message below, then press “Open LINE”. On a phone LINE opens with this message; on a computer LINE shows a QR code to scan with your phone. If LINE does not open, copy the message into the chat, or call us.
Add us on LINE: @x2525 · Call 062-195-1909