LINE: ask a price

SCG

SCG GTB-G glass-wool duct liner

Glass-wool board for lining the inside of air-conditioning ducts, faced with black glass tissue; it absorbs air and fan noise travelling along the duct.

Thermal conductivity (λ)
0.032 W/m·K 48 kg/m³ at 24 °C mean (test standard not stated)
Service temperature range
4 – 230 °C

Ask us on LINE about the sizes we supply and the price.

Ask about this product

Product details

Duct and HVAC insulationGlass wool (fibreglass)SCG

Green glass-wool board faced with black glass tissue · for lining ducts

Thermal conductivity (λ)
0.032 W/m·K 48 kg/m³ at 24 °C mean (test standard not stated)
Service temperature range
4 – 230 °C

What is it?

SCG GTB-G is a semi-rigid green glass-wool board faced on one side with black glass tissue. It lines the inside of ducts to absorb noise carried along them, with the faced side towards the airstream. The maker states it is for air velocities up to 10 m/s (2,000 fpm) and 4–230 °C. Density 48 kg/m³; 25 and 50 mm thick.

What is it made of?

Glass wool (fibreglass) · Facing: Black glass tissue · Board

Limitations to know

The maker states a maximum air velocity of 10 m/s (2,000 fpm) and a temperature range of 4–230 °C.

Where does the data come from?

SCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner)

Technical data from the manufacturer's documents SCG · Checked 12 Oct 2026

Technical specifications

All values come from the manufacturer's documents, with conditions and test standards. Values the documents do not state are not shown.

PropertyValueConditions / standardSource
Thermal conductivity (λ)0.032 W/m·K48 kg/m³ at 24 °C mean (test standard not stated)SCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner), p. 10
Service temperature range4 – 230 °C—SCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner), p. 9
Maximum air velocity10 m/s (2,000 fpm)—SCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner), p. 9
FacingBlack glass tissue—SCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner), p. 10
Reaction to fireFS < 25 · SD < 50flame spread / smoke developed (surface burning characteristic) · ASTM E84SCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner), p. 11
Moisture sorption0.2% by volumeASTM C1104SCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner), p. 11
Mould or fungus growthWill not support or promoteASTM C665SCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner), p. 11
Standards / certificationMade to TIS 486, 487 and ASTM standardsThe catalogue notes that certifications are available for selected productsSCG thermal insulation catalogue for air-conditioning and industrial work (pages 8–11: duct liner), p. 9

Applications

Highlights

  • Faced with black glass tissue
  • Absorbs noise inside ducts
  • 48 kg/m³; 25 and 50 mm thick

Installation overview

  1. Line every side of the duct section designed to be lined, with board joints butted tight
  2. Face the facing towards the airstream; apply adhesive to at least 90% of the board area on the duct side
  3. Add enough mechanical fasteners for the duct size
  4. Cut boards to the inner duct size with a sharp knife so edges and facing are not damaged

Always follow the manufacturer's installation and safety instructions.

Manufacturer documents

Not sure which model suits your job?

Send the area details or site photos — we'll suggest the model and quantity

Ask via LINE